Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Valve Type Arrester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Type | Surge Protector |
---|---|
Product Series | VALVETRAB MS |
IEC Category | II |
EN Type | T2 |
IEC Power System | TN-S, TT |
Type | DIN Rail Module, Split, Removable |
Number of Poles | 4 |
Surge Protector Fault Indicator | With Visible Status Indicator Window |
Insulation Characteristics | |
Overvoltage Category | III |
Pollution Degree | 2 |
Rated Frequency (fN) | 50 Hz (60 Hz) |
Connection Type | Screw Connection |
Thread | M5 |
Tightening Torque | 3 Nm (1.5 mm² ... 16 mm²) |
4.5 Nm (25 mm² ... 35 mm²) | |
Strip Length | 16 mm |
Flexible Conductor Cross-Section | 1.5 mm² ... 25 mm² |
Rigid Conductor Cross-Section | 1.5 mm² ... 35 mm² |
AWG Connection Range | 15 ... 2 |
Connection Type (Forked Cable Terminal) | |
Flexible Conductor Cross-Section | 1.5 mm² ... 16 mm² |
Dimensions | |
Width | 71 mm |
Height | 89.8 mm |
Depth | 65.7 mm (7.5 mm including DIN Rail) |
Horizontal Pin Pitch | 4 sections |
Color | Black (RAL 9005) |
Flammability Rating (UL 94) | V-0 |
CTI Value (Material) | 600 |
Insulation Material | PA 6.6 / PBT |
Material Group | I |
Enclosure Material | PA 6.6 / PBT |
Protection Channels | L-N, L-PE, N-PE |
Direction of Action | 3L-N & N-PE |
Rated Voltage (UN) | 240/415 V AC (TN-S), 240/415 V AC (TT) |
Rated Frequency (fN) | 50 Hz (60 Hz) |
Maximum Continuous Operating Voltage (UC) | 275 V AC (L-N), 275 V AC (L-PE), 260 V AC (N-PE) |
Rated Load Current (IL) | 80 A |
Leakage Current (IPE) | ≤ 5 µA |
Standby Power Consumption (PC) | ≤ 360 mVA |
Nominal Discharge Current (In) (8/20 µs) | 20 kA |
Maximum Discharge Current (Imax) (8/20 µs) | 40 kA |
Rated Short-Circuit Current (ISCCR) | 25 kA |
Voltage Protection Level (Up) (L-N) | ≤ 1.35 kV |
Voltage Protection Level (Up) (L-PE) | ≤ 1.6 kV |
Voltage Protection Level (Up) (N-PE) | ≤ 1.5 kV |
Residual Voltage (Ures) (L-N) | ≤ 1.35 kV (at In), ≤ 1.1 kV (at 10 kA), ≤ 1 kV (at 5 kA), ≤ 0.9 kV (at 3 kA) |
Residual Voltage (Ures) (L-PE) | ≤ 1.6 kV (at In), ≤ 1.2 kV (at 10 kA), ≤ 1 kV (at 5 kA), ≤ 0.9 kV (at 3 kA) |
Residual Voltage (Ures) (N-PE) | ≤ 0.4 kV (at In), ≤ 0.25 kV (at 10 kA), ≤ 0.15 kV (at 5 kA), ≤ 0.1 kV (at 3 kA) |
TOV Response under UT (L-N) | 335 V AC (5 sec / withstand mode), 440 V AC (120 min / safe fail mode) |
TOV Response under UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
Response Time (tA) (L-N) | ≤ 25 ns |
Response Time (tA) (L-PEN) | ≤ 100 ns |
Response Time (tA) (N-PE) | ≤ 100 ns |
Max Backup Fuse (with V-Type Connection) | 80 A (gG) |
Max Backup Fuse (with Branch Wiring) | 125 A (gG) |
Environmental Conditions | |
Protection Degree | IP20 (only with all connection positions used) |
Operating Temperature | -40 °C ... 80 °C |
Storage/Transport Temperature | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Humidity (Operating) | 5% ... 95% |
Shock (Operating) | 25g (half sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operating) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL Specifications | |
Max Continuous Operating Voltage (MCOV) (L-L) | 550 V AC |
Max Continuous Operating Voltage (MCOV) (L-N) | 275 V AC |
Max Continuous Operating Voltage (MCOV) (L-G) | 275 V AC |
Max Continuous Operating Voltage (MCOV) (N-G) | 260 V AC |
Nominal Discharge Current In (L-L) | 20 kA |
Nominal Discharge Current In (L-N) | 20 kA |
Nominal Discharge Current In (L-G) | 20 kA |
Nominal Discharge Current In (N-G) | 20 kA |
Protection Channels | L-L, L-N, L-G, N-G |
Rated Voltage | 230/400 V AC |
Power Distribution System | Wye |
Rated Frequency | 50/60 Hz |
Measured Limiting Voltage MLV (L-L) | 2720 V |
Measured Limiting Voltage MLV (L-N) | 1910 V |
Measured Limiting Voltage MLV (L-G) | 2630 V |
Measured Limiting Voltage MLV (N-G) | 1370 V |
SPD Model | 4CA |
UL Connection Data | |
Tightening Torque | 30 lbf-in. |
AWG Connection Range | 14 ... 2 |
Standards/Regulations | IEC 61643-11, EN 61643-11 |
Notes | 2011, 2012 |
Installation Type | DIN Rail: 35 mm |